Project

Contamination Control Manufacturing Facility, North East

Multiple jobs carried out on a contamination control manufacturing facility in the North East of the UK.

Project Overview

Design, supply, installation, testing & commissioning of a new automatic fire sprinkler system.

New sprinkler installation NFPA 13 | NFPA 30
Industrial

What we did

Design, supply, installation, testing & commissioning of a new automatic fire sprinkler system designed in accordance with NFPA 13 & NFPA 30 and insurer amendments. Roof design to NFPA 30 18.3mm/min over 270m² | Racks design to NFPA 30 Scheme B | Offices to NFPA 13 4.1mm/min over 139m². The system is fed from duplicate Diesel engine driven fire pumps drawing water from duplicate 500m³ effective capacity water storage tanks. The system is subdivided into four installations.