An Armstrong Priestley Project at Scientific Games
Scientific Games
Project Specifics
Roof sprinkler protection provided throughout the warehouse, via one 200mm wet installation control valve, utilising K480 ESFR sprinkler heads. Supplied from one diesel fire pump, rated at 2,500 USGpm at 115psi, housed in steel fabricated enclosure, drawing water from a single 615m3 sprinkler tank.