Case Study

An Armstrong Priestley Project at Contec

Contec

Project Specifics

Design, supply, installation, testing & commissioning of a new automatic fire sprinkler system designed in accordance with NFPA 13 & NFPA 30 and insurer amendments. Roof design to NFPA 30 18.3mm/min over 270m² | Racks design to NFPA 30 Scheme B | Offices to NFPA 13 4.1mm/min over 139m². The system is supplied by two diesel fire pumps drawing water from two 500m³ capacity water storage tanks. The system is subdivided into four installations.